HOME > SUPPORT > KNOWLEDGE > WHAT IS 4-20 mA

4-20 mA CURRENT LOOPS

Despite the growing focus on digital communication technologies, the 4-20 mA analog output remains one of the most dominant types of analog output in the industry today. Another popular type of analog output is the  0-10 VDC output.

There exist different types of 4-20 mA loops, where the two-wire loop version is by far the most widespread. Three and four wire 4-20 mA variants are similar in their fundamental working principle and thus we will not treat them here.

The basic concept behind the two-wire 4-20 mA current loop is to power the device through the same two-wires that are part of the analog measurement circuit.

An example of a two-wire current loop is shown in the figure below.



4-20 mA current loop for pressure transmitter

The main current loop comprises a DC power supply, a 250 Ω resistor and a transmitter connected in series.

A voltmeter is connected in parallel with the resistor to measure the voltage across it. 

The transmitter regulates the amount of current that flows through the circuit as a function the process variable measured by the transmitter, e.g. temperature or pressure. A typical linear analog output scaling for a 1 bar full-scale pressure transmitter is a loop current of 4 mA at 0 bar and 20 mA at 1 bar.

Since the amount of current is the same throughout the entire main loop at any given point in time, the voltage across the 250 Ω resistor becomes a direct measure of the process variable. For example, if the pressure is 0 bar, the transmitter regulates the loop current to 4 mA and consequently the voltage measured across the resistor is 1 V (due to Ohm’s law – link here). Similarly, if the pressure is 1 bar the transmitter regulates the loop current to 20 mA which corresponds to 5 V across the resistor.   


Advantages of 4-20mA current loops


  • Simple installation
  • Robust against background electrical noise
  • Can travel long distances without causing signal degradation
  • Easy fault-detection if the loop is broken (loop current < 4 mA)


Disadvantages of 4-20 mA current loops


  • Only one transmitter can be part of a current loop
  • Multiple current loops tend to increase the risk of creating unwanted ground loops
  • Cost of installation is directly proportional with the number of loops – no high-volume advantage


Pressure transmitter with 4-20mA output

4-20 mA pressure measurement products from Sens4

■  Ceramic & Steel diaphragm

■  Programmable features

■  Precision performance


> For more information

Do you have questions or need help configuring the right products?

Sens4 on facebook
Sens4 on LinkedIn
Sens4 on Twitter
Sens4 on Youtube

Our passion | Your value™


Copyright © 2019 - Sens4 A/S

Sens4 A/S  Nordre Strandvej 119G  3150 Hellebaek  Denmark

Tel: +45 8844 7044  > Email to Sens4

HOME   |   ABOUT   |   NEWS   |   PRODUCTS   |   SHOP  |  INDUSTRIES   |   SUPPORT   |  CONTACT   |   KNOWLEDGE   |   CAREERS   |  COOKIES  |  TERMS & CONDITIONS  |   PRIVACY & LEGAL

CVR: 39389029